Inertech 120second discharge systems - ISO 14520

Winter 2016

ISO 14520 allows 120 second discharge time.

(EN 15004 is due to follow in the next year)

With Inertech this gives even more system cost savings:

  • Smaller pressure vents


  • Smaller discharge pipes


  • Longer pipe runs


Discharge times under different European standards for Inert Gases – 60s and 120s:

BS EN 15004-1: 2008: ‘The discharge time required to achieve 95% of the design concentration for non-liquefied extinguishants shall not exceed 60s at 20 o C…’

ISO 14520-1: 2015: ‘For inert gas the discharge time is the time required to discharge from the nozzles 95%....shall not exceed… 120 seconds for Class A hazards...’

MyFSL

Login to gain access to an online quotation tool, technical datasheets and marketing brochures

Log in
MyFSL

Online Video Support

What you need, when you need it!

Installation & demonstration versions are now available with more to follow...

View Here
Online Video Support

FSL Inert System Benefits

Our Inert 200 bar & 300 bar systems are able to comply with both, ISO 14520-1 & BS EN 15004-1 standards to achieve 60 and 120 second discharge without making any changes to equipment.

This is due to the pressure controller which regulates the pressure from 300 bar to 60 bar.

The discharge times can be controlled through the changing of the nozzle orifice plate that is placed within our discharge nozzles.

  • No controlling restrictor orifice plates


  • No pilot cylinders – selector valves driven from discharge manifold


  • Pressure controlled discharge optimised for both 60 & 120 second discharge


  • IG-01, IG-100, IG-55 & IG-541 all using the same hardware


  • Reduced noise & turbulence during discharge


  • No actuation on check valves on multi-room systems using selector valves


Autumn 2017

A simple new addition to FSL Inertech
A simple new addition to FSL Inertech

A simple new addition to FSL Inertech makes cylinder exchange a breeze! Adding a simple sticker to the master actuation...

Read More

FSL to attend Data Centre World 2018
FSL to attend Data Centre World 2018

We are pleased to announce that we will exhibiting at Data Centre World 2018. Data Centre World is the world’s largest and...

Read More

FSL at Safety Expo Bergamo - Italy
FSL at Safety Expo Bergamo - Italy

FSL at Safety Expo Bergamo - Italy FSL enjoyed a successful visit to Safety Expo Bergamo 2017. Speaking with our customers...

Read More

News Archive

  1. Autumn 2017
  2. Summer 2017
  3. Spring 2017
  4. Winter 2017
  5. Autumn 2016
  6. Summer 2016
  7. Winter 2016
  8. Autumn 2015
  9. Summer 2015
  10. Spring 2015
  11. Autumn 2014
  12. Winter 2014

Home  /  About us  /  News  /  Products  /  Training  /  MyFSL  /  Contact us  /  Terms and Conditions  /  Approvals

Loss Prevention Certification Board Loss Prevention Certification Board UKAS Quality Management 007 Conformité Européenne

Copyright 2013 Firetec Systems Ltd. Company registration No. 08509442.
Registered in England and Wales